Stations

Stations – Available Capacity Thermal kVA SC Cap.
Stn Description MVA MVA*
2 Port Arthur TS #1 (25kV) 31.0 1.5
4 Vickers St SS (4kV) 2.0 39.2
5 Donald St SS (4kV) 2.0 32.9
10 Fort William TS (25kV) 69.7 229.7
11 High St SS (4kV) 3.5 111.4
12 Camelot St SS (4kV) 4.0 100.6
14 Algoma St SS (4kV) 2.1 99.3
16 MacDonnel St SS (4kV) 2.2 53.6
17 Birch TS (25kV) 65.1 152.7
18 Balsam St T2 (12kV) 3.1 333.8
19 Broadway Ave SS (12kV) 3.2 163.8
21 Windemere Ave SS (4kV) 2.5 62.0
23 Alice Ave SS (12kV) 3.4 158.6
36 Mapleward Rd SS (12kV) 0.9 152.2
1501 Kenora MTS (12kV) 28.5 105.9

NOTE: Contact SYNERGY NORTH to determine the feeder designation which applies to your project

*Estimated based on the use of inverter connected generation

Terms & Conditions of Service

Standard Contractual Terms and Conditions of Service Micro Small Mid-Sized Large
Standard Terms and Conditions

Embedded Generation Inquiries

Daniel Dillon, P.Eng
Distribution Engineer
(807) 343-1037
ddillon@synergynorth.ca